A gateway assembly includes one gateway (the left most unit) and multiple I/O Expansion modules. Module stacking is done from left to right. Up to 8 I/O Expansion Modules can be supported in one gateway assembly.  
 
A gateway assembly includes one gateway (the left most unit) and multiple I/O Expansion modules. Module stacking is done from left to right. Up to 8 I/O Expansion Modules can be supported in one gateway assembly.  
 
The modules are interconnected using Compulab’s proprietary StackLink expansion connector that extends a series of the IOT-DIN-IMX8PLUS interfaces, creating a chain of peripherals.
 
The modules are interconnected using Compulab’s proprietary StackLink expansion connector that extends a series of the IOT-DIN-IMX8PLUS interfaces, creating a chain of peripherals.
 +
 +
=== I/O Expansion Modules Stacking Rules ===
 +
* There can be up-to 8 I/O Expansion Modules in one assembly
 +
* IFM-WB modules can only be installed in position A (next to main gateway)
 +
* There can be up-to 3 (in total) modules of types IFM-RS485, IFM-RS232, IFM-WB
 +
* There can be up-to 4 IFM-DI8O8 modules
 +
* There can be only 1 IFM-ADC8 module
  
 
= I/O Modules Configuration =
 
= I/O Modules Configuration =
Line 84: Line 91:
  
 
StackLink configurator script stores stack detection info log in the following designated location:
 
StackLink configurator script stores stack detection info log in the following designated location:
 +
<!--
 
<pre>
 
<pre>
 
/run/iotdin-imx8p/log/iotdin-imx8p.stack.log*
 
/run/iotdin-imx8p/log/iotdin-imx8p.stack.log*
 +
</pre>
 +
-->
 +
<pre>
 +
/run/iotdin-imx8p/log/iotdin-imx8p.stack.log.<YYYYMMDD_HHMMSS>
 
</pre>
 
</pre>
  
Line 94: Line 106:
 
In case of invalid IFM stack status:
 
In case of invalid IFM stack status:
 
# Check the stack detection log
 
# Check the stack detection log
 +
# Double check if a desired stack conforms the [[IOT-DIN-IMX8PLUS:_Debian_Linux:_I/O_Modules_Guide#I.2FO_Expansion_Modules_Stacking_Rules | Stacking Rules]]
 
# Verify proper mechanical attachment of modules
 
# Verify proper mechanical attachment of modules
 
# Contact technical support
 
# Contact technical support
Line 103: Line 116:
 
= IFM-DI8O8 =
 
= IFM-DI8O8 =
 
IFM-DI8O8 module provides an isolated block of eight digital inputs and a block of eight digital outputs.<br>
 
IFM-DI8O8 module provides an isolated block of eight digital inputs and a block of eight digital outputs.<br>
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed IFM-DI8O8 modules and create necessary access files in the front-plane directory. For additional details please refer to the [[IOT-DIN-IMX8PLUS: Debian Linux: I/O Modules Guide#Configuration|Configuration chapter]].<br>
+
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed IFM-DI8O8 modules and create necessary access files in the front-plane directory. For additional details please refer to the [[IOT-DIN-IMX8PLUS:_Debian_Linux:_I/O_Modules_Guide#I.2FO_Modules_Configuration|Configuration chapter]].<br>
  
 
Use '''diodetect''' command to get an overview of all available Digital Inputs and Outputs:
 
Use '''diodetect''' command to get an overview of all available Digital Inputs and Outputs:
Line 173: Line 186:
 
</pre>
 
</pre>
  
 +
= IFM-ADC8 =
 +
IFM-ADC8 provides eight single-ended analog input channels (0-7), divided into two blocks of 4. Inputs operate between 0-10V or 4-20mA ranges for use with industrial sensors. Each block can be set into current or voltage input mode via jumper.<br>
 +
 +
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the [[IOT-DIN-IMX8PLUS:_Debian_Linux:_I/O_Modules_Guide#I.2FO_Modules_Configuration|Configuration chapter]].<br>
 +
 +
'''Example'''<br>
 +
Рead a detected value of channel '''5''' of IFM-ADC8 module installed in slot '''A''':<br>
 +
<pre>
 +
compulab@compulab-imx8mp:~$ X=5 ; slot=A
 +
compulab@compulab-imx8mp:~$ sudo cat /run/iotdin-imx8p/stack/frontplane/${slot}/access/adc$((X/4))/in_voltage$((X%4))_raw
 +
</pre>
 +
<!--
 
= IFM-ADC =
 
= IFM-ADC =
 
IFM-ADC8 provides eight single-ended analog input channels, divided into two blocks of 4. Inputs operate between 0-10V or 4-20mA ranges for use with industrial sensors. Each block can be set into current or voltage input mode via jumper.<br>
 
IFM-ADC8 provides eight single-ended analog input channels, divided into two blocks of 4. Inputs operate between 0-10V or 4-20mA ranges for use with industrial sensors. Each block can be set into current or voltage input mode via jumper.<br>
Line 209: Line 234:
 
| ../run/iotdin-imx8p/stack/frontplane/A/access/adc1/in_voltage3_raw
 
| ../run/iotdin-imx8p/stack/frontplane/A/access/adc1/in_voltage3_raw
 
|}
 
|}
 +
-->
  
 
= IFM-RS485 =
 
= IFM-RS485 =
 
IFM-RS485 I/O module provides four half-duplex RS485 ports.</br>
 
IFM-RS485 I/O module provides four half-duplex RS485 ports.</br>
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the [[IOT-DIN-IMX8PLUS: Debian Linux: I/O Modules Guide#Configuration|Configuration chapter]].<br>
+
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the [[IOT-DIN-IMX8PLUS:_Debian_Linux:_I/O_Modules_Guide#I.2FO_Modules_Configuration|Configuration chapter]].<br>
  
 
===Example===
 
===Example===
Line 233: Line 259:
  
 
IFM-RS232 I/O module provides four 2-wire RS232 ports.</br>
 
IFM-RS232 I/O module provides four 2-wire RS232 ports.</br>
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the [[IOT-DIN-IMX8PLUS: Debian Linux: I/O Modules Guide#Configuration|Configuration chapter]].<br>
+
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the [[IOT-DIN-IMX8PLUS:_Debian_Linux:_I/O_Modules_Guide#I.2FO_Modules_Configuration|Configuration chapter]].<br>
  
 
===Example===
 
===Example===
Line 249: Line 275:
 
</pre>
 
</pre>
 
Use <code>/run/iotdin-imx8p/stack/frontplane/D/access/tty'''X'''</code> to access port #'''X'''
 
Use <code>/run/iotdin-imx8p/stack/frontplane/D/access/tty'''X'''</code> to access port #'''X'''
 +
 +
= IFM-WB =
 +
 +
IFM-WB I/O module features one 802.11ax WiFi and one Bluetooth 5.3 BLE interfaces.</br>
 +
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the [[IOT-DIN-IMX8PLUS:_Debian_Linux:_I/O_Modules_Guide#I.2FO_Modules_Configuration|Configuration chapter]].<br>
 +
{{Note|IFM-WB module can only be installed in position A (next to main gateway)}}
 +
 +
For an IFM-WB module installed in slot A the configurator script will create the following access files:
 +
<pre>
 +
/run/iotdin-imx8p/stack/frontplane/
 +
|-- A
 +
|  |-- access
 +
|  |  |-- bluetooth -> /sys/class/bluetooth/hci0
 +
|  |  `-- wlan -> /sys/class/net/wlan0
 +
|  `-- type.WB
 +
</pre>
 +
 +
=== Example ===
 +
* Display WiFi network interface info
 +
<pre>
 +
compulab@compulab-imx8mp:~$ wlan=$(basename $(readlink -f /run/iotdin-imx8p/stack/frontplane/A/access/wlan))
 +
compulab@compulab-imx8mp:~$ sudo ifconfig ${wlan}
 +
compulab@compulab-imx8mp:~$ sudo iwconfig ${wlan}
 +
</pre>
 +
* Display Bluetooth interface info
 +
<pre>
 +
compulab@compulab-imx8mp:~$ bt=$(basename $(readlink -f /run/iotdin-imx8p/stack/frontplane/A/access/bluetooth))
 +
compulab@compulab-imx8mp:~$ hciconfig ${bt}
 +
</pre>
 +
 +
== WiFi ==
 +
=== Enable/Disable WiFi Interface ===
 +
* To enable WiFi interface:
 +
:<pre>compulab@compulab-imx8mp:~$ sudo nmcli radio wifi on</pre>
 +
* To disable WiFi interface:
 +
:<pre>compulab@compulab-imx8mp:~$ sudo nmcli radio wifi off</pre>
 +
 +
=== Network Scanning ===
 +
* Sample WiFi scanning:
 +
:<pre>compulab@compulab-imx8mp:~$ nmcli dev wifi list</pre>
 +
:The output will show the list of Access Points and Ad-Hoc cells in range.
 +
 +
=== Connecting to Access Point ===
 +
In the following example:
 +
* Replace <SSID> and <PASSWORD> with the actual access point parameters:
 +
:<pre>compulab@compulab-imx8mp:~$ sudo nmcli device wifi connect <SSID> password <PASSWORD> name WifiCon</pre>
 +
* Disconnect wireless network:
 +
:<pre>compulab@compulab-imx8mp:~$ sudo nmcli connection down WifiCon</pre>
 +
* Connect wireless network again:
 +
:<pre>compulab@compulab-imx8mp:~$ sudo nmcli connection up WifiCon</pre>
 +
 +
=== Creating Access Point ===
 +
{{Note|Debian 12<br>ipv4 forwarding must be turned on manually}}
 +
* Enable port forwarding:
 +
:<pre>compulab@compulab-imx8mp:~$ sudo sed -i 's/^#\(net.ipv[4,6].*forward\)/\1/' /etc/sysctl.conf</pre>
 +
 +
* Enable wireless AP (replace ''<SSID>'' and ''<PASSWORD>'' with desired access point parameters):
 +
:<pre>sudo nmcli device wifi hotspot ssid <SSID> password <PASSWORD> con-name HotspotCon</pre>
 +
* Disable wireless AP:
 +
:<pre>compulab@compulab-imx8mp:~$ sudo nmcli connection down HotspotCon</pre>
 +
* Enable wireless AP again:
 +
:<pre>compulab@compulab-imx8mp:~$ sudo nmcli connection up HotspotCon</pre>

Latest revision as of 15:31, 16 July 2024

Overview

IOT-DIN-IMX8PLUS supports up to eight I/O Expansion Modules that can be stacked with the main gateway in order to extend the feature set of the system. A gateway assembly includes one gateway (the left most unit) and multiple I/O Expansion modules. Module stacking is done from left to right. Up to 8 I/O Expansion Modules can be supported in one gateway assembly. The modules are interconnected using Compulab’s proprietary StackLink expansion connector that extends a series of the IOT-DIN-IMX8PLUS interfaces, creating a chain of peripherals.

I/O Expansion Modules Stacking Rules

  • There can be up-to 8 I/O Expansion Modules in one assembly
  • IFM-WB modules can only be installed in position A (next to main gateway)
  • There can be up-to 3 (in total) modules of types IFM-RS485, IFM-RS232, IFM-WB
  • There can be up-to 4 IFM-DI8O8 modules
  • There can be only 1 IFM-ADC8 module

I/O Modules Configuration

I/O expansion modules are managed as a front-plane of virtual slots that map device access files to physical I/O modules per their positions in the stack.
During O/S boot IOT-DIN-IMX8PLUS automatically runs the StackLink configurator script that detects I/O modules and configures the virtual device files used to address the hardware.
The script creates the IFM front-plane file directory that includes type and access files for all populated stack slots.

IFM Front-Plane

During O/S boot the StackLink configurator script creates the IFM front-plane file directory that includes type and access files for all populated stack slots (from A to last populated slot).

/run/iotdin-imx8p/stack/frontplane

Front-plane directory structure

Example I/O modules stack:


+----------+-------+-------+-------+-------+
|  Slot #  |   A   |   B   |   C   |   D   |
+----------+-------+-------+-------+-------+
| IFM Type | ADC8  | DI8O8 | RS485 | RS232 |
+----------+-------+-------+-------+-------+

Front-plane file directory:

/run/iotdin-imx8p/stack/frontplane
|-- A
|   |-- access
|   |   |-- adc0 -> /sys/bus/iio/devices/iio:device0
|   |   `-- adc1 -> /sys/bus/iio/devices/iio:device1
|   `-- type.ADC8
|-- B
|   |-- access
|   |   |-- di.map
|   |   |-- do.map
|   |   `-- gpiochip -> /dev/gpiochip6
|   `-- type.DI8O8
|-- C
|   |-- access
|   |   |-- tty0 -> /dev/ttyIFM_RSx_0_0
|   |   |-- tty1 -> /dev/ttyIFM_RSx_0_1
|   |   |-- tty2 -> /dev/ttyIFM_RSx_0_2
|   |   `-- tty3 -> /dev/ttyIFM_RSx_0_3
|   `-- type.RS485
`-- D
    |-- access
    |   |-- tty0 -> /dev/ttyIFM_RSx_1_0
    |   |-- tty1 -> /dev/ttyIFM_RSx_1_1
    |   |-- tty2 -> /dev/ttyIFM_RSx_1_2
    |   `-- tty3 -> /dev/ttyIFM_RSx_1_3
    `-- type.RS232

Stack Detection Status

StackLink configurator script provides indication of I/O modules stack detection status using IOT-DIN-IMX8PLUS power LED:

Power LED Status Remarks
Blinking Blue Recognized and valid configuration Normal operation
Blinking Amber Unrecognized I/O module or invalid configuration Check the log for details

Stack Detection Info

StackLink configurator script stores stack detection info log in the following designated location:

/run/iotdin-imx8p/log/iotdin-imx8p.stack.log.<YYYYMMDD_HHMMSS>

Stack Troubleshooting


Admolition warning.png DO NOT attach or detach I/O Expansion modules while the gateway is connected to DC power! Disconnect all power sources from the gateway before attaching or detaching I/O modules.

In case of invalid IFM stack status:

  1. Check the stack detection log
  2. Double check if a desired stack conforms the Stacking Rules
  3. Verify proper mechanical attachment of modules
  4. Contact technical support

IFM Backplane


/run/iotdin-imx8p/stack/backplane directory stores the system information about the physical hardware devices installed in the stack. These files should not be altered.

IFM-DI8O8

IFM-DI8O8 module provides an isolated block of eight digital inputs and a block of eight digital outputs.
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed IFM-DI8O8 modules and create necessary access files in the front-plane directory. For additional details please refer to the Configuration chapter.

Use diodetect command to get an overview of all available Digital Inputs and Outputs:

compulab@compulab-imx8mp:~$ /opt/iotdin-imx8p/shell/diodetect
Main Gateway:   DI2O2   (2x DI; 2x DO)
Stack Slot B:   DI8O8   (8x DI; 8x DO)

Use dioget and dioset commands to access digital inputs and digital outputs.
It is recommended to set the following alias for more convenient work:

compulab@compulab-imx8mp:~$ dioget=/opt/iotdin-imx8p/shell/dioget
compulab@compulab-imx8mp:~$ dioset=/opt/iotdin-imx8p/shell/dioset

Reading Digital Inputs

Setup alias for more convenient work:

compulab@compulab-imx8mp:~$ dioget=/opt/iotdin-imx8p/shell/dioget
compulab@compulab-imx8mp:~$ sudo ${dioget} -h
Usage: dioget [options] <command>

Read digital input state from a Digital I/O (DIO) module

Command:
 -m <module> <offset>
        module: DIO module location:
            m|M - Main Gateway
            a|A - Virtual slot A
            ...
            h|H - Virtual slot H
        offset: input pin offset: <0..MaxOffset>
Options:
 -h:    display this help and exit

Example
Read state of input pin IN_4 on IFM-DI8O8 installed in slot B:

compulab@compulab-imx8mp:~$ sudo ${dioget} -m B 4

Setting Digital Outputs

Setup alias for more convenient work:

compulab@compulab-imx8mp:~$ dioset=/opt/iotdin-imx8p/shell/dioset
compulab@compulab-imx8mp:~$ sudo ${dioset} -h
Usage: dioset [options] <command>

Set the digital output state of a Digital I/O (DIO) module

Command:
 -m <module> <offset>  <state>
        module: DIO module location:
            m|M - Main Gateway
            a|A - Virtual slot A
            ...
            h|H - Virtual slot H
        offset: output pin offset: <0..MaxOffset>
        state:  output pin state to be set: <0|1>
Options:
 -h:    display this help and exit

Example
Setting output pin OUT_4 to HIGH state on IFM-DI8O8 installed in slot B:

compulab@compulab-imx8mp:~$ sudo ${dioset} -m B 4 1

IFM-ADC8

IFM-ADC8 provides eight single-ended analog input channels (0-7), divided into two blocks of 4. Inputs operate between 0-10V or 4-20mA ranges for use with industrial sensors. Each block can be set into current or voltage input mode via jumper.

During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the Configuration chapter.

Example
Рead a detected value of channel 5 of IFM-ADC8 module installed in slot A:

compulab@compulab-imx8mp:~$ X=5 ; slot=A
compulab@compulab-imx8mp:~$ sudo cat /run/iotdin-imx8p/stack/frontplane/${slot}/access/adc$((X/4))/in_voltage$((X%4))_raw

IFM-RS485

IFM-RS485 I/O module provides four half-duplex RS485 ports.
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the Configuration chapter.

Example

For an IFM-RS485 module installed in slot C the configurator script will create the following access files:

/run/iotdin-imx8p/stack/frontplane/
|-- C
|   |-- access
|   |   |-- tty0
|   |   |-- tty1
|   |   |-- tty2
|   |   `-- tty3
|   `-- type.RS485

Use /run/iotdin-imx8p/stack/frontplane/C/access/ttyX to access port #X

IFM-RS232

IFM-RS232 I/O module provides four 2-wire RS232 ports.
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the Configuration chapter.

Example

For an IFM-RS232 module installed in slot D the configurator script will create the following access files:

/run/iotdin-imx8p/stack/frontplane/
|-- D
|   |-- access
|   |   |-- tty0
|   |   |-- tty1
|   |   |-- tty2
|   |   `-- tty3
|   `-- type.RS232

Use /run/iotdin-imx8p/stack/frontplane/D/access/ttyX to access port #X

IFM-WB

IFM-WB I/O module features one 802.11ax WiFi and one Bluetooth 5.3 BLE interfaces.
During O/S boot IOT-DIN-IMX8PLUS will automatically detect installed I/O modules and create necessary access files in the front-plane directory. For additional details please refer to the Configuration chapter.

Admolition note.png IFM-WB module can only be installed in position A (next to main gateway)

For an IFM-WB module installed in slot A the configurator script will create the following access files:

/run/iotdin-imx8p/stack/frontplane/
|-- A
|   |-- access
|   |   |-- bluetooth -> /sys/class/bluetooth/hci0
|   |   `-- wlan -> /sys/class/net/wlan0
|   `-- type.WB

Example

  • Display WiFi network interface info
compulab@compulab-imx8mp:~$ wlan=$(basename $(readlink -f /run/iotdin-imx8p/stack/frontplane/A/access/wlan))
compulab@compulab-imx8mp:~$ sudo ifconfig ${wlan}
compulab@compulab-imx8mp:~$ sudo iwconfig ${wlan}
  • Display Bluetooth interface info
compulab@compulab-imx8mp:~$ bt=$(basename $(readlink -f /run/iotdin-imx8p/stack/frontplane/A/access/bluetooth))
compulab@compulab-imx8mp:~$ hciconfig ${bt}

WiFi

Enable/Disable WiFi Interface

  • To enable WiFi interface:
compulab@compulab-imx8mp:~$ sudo nmcli radio wifi on
  • To disable WiFi interface:
compulab@compulab-imx8mp:~$ sudo nmcli radio wifi off

Network Scanning

  • Sample WiFi scanning:
compulab@compulab-imx8mp:~$ nmcli dev wifi list
The output will show the list of Access Points and Ad-Hoc cells in range.

Connecting to Access Point

In the following example:

  • Replace <SSID> and <PASSWORD> with the actual access point parameters:
compulab@compulab-imx8mp:~$ sudo nmcli device wifi connect <SSID> password <PASSWORD> name WifiCon
  • Disconnect wireless network:
compulab@compulab-imx8mp:~$ sudo nmcli connection down WifiCon
  • Connect wireless network again:
compulab@compulab-imx8mp:~$ sudo nmcli connection up WifiCon

Creating Access Point

Admolition note.png Debian 12
ipv4 forwarding must be turned on manually
  • Enable port forwarding:
compulab@compulab-imx8mp:~$ sudo sed -i 's/^#\(net.ipv[4,6].*forward\)/\1/' /etc/sysctl.conf
  • Enable wireless AP (replace <SSID> and <PASSWORD> with desired access point parameters):
sudo nmcli device wifi hotspot ssid <SSID> password <PASSWORD> con-name HotspotCon
  • Disable wireless AP:
compulab@compulab-imx8mp:~$ sudo nmcli connection down HotspotCon
  • Enable wireless AP again:
compulab@compulab-imx8mp:~$ sudo nmcli connection up HotspotCon